Voltage Flicker Analysis due to the Starting of 250 kW Three-Phase Induction Motor at the Karah Pump House, Surabaya

Authors

  • Reza Sarwo Widagdo Universitas 17 Agustus 1945 Surabaya, Indonesia Author
  • Puji Slamet Universitas 17 Agustus 1945 Surabaya, Indonesia Author
  • Imam Suri Tauladan Universitas Riau, Indonesia Author
  • Lutfi Agung Swarga Universitas 17 Agustus 1945 Surabaya, Indonesia Author
  • Bima Gilang Pratama Universitas 17 Agustus 1945 Surabaya, Indonesia Author
  • Izzah Aula Wardah Universitas 17 Agustus 1945 Surabaya, Indonesia Author

DOI:

https://doi.org/10.35143/elementer.v12i1.7024

Abstract

This study aims to analyze the causes of voltage flicker during the starting process of a three-phase induction motor at the Karah Pump House in Surabaya. The use of high power induction motors is essential for supporting flood control systems; however, conventional starting methods such as Direct On Line (DOL) and Star-Delta can generate high inrush currents that negatively affect power quality. The research evaluates starting current characteristics, distribution system impedance, and the resulting voltage flicker based on IEC standards. The analysis shows that the DOL method produces greater voltage drop and voltage flicker compared to the Star Delta method. Although the Star-Delta method is able to reduce voltage disturbances, both methods still have the potential to exceed standard flicker limits if the distribution system is not equipped with adequate mitigation devices. Therefore, proper starting current control is an important factor in maintaining power quality and ensuring the stability of the pump house distribution system.

Author Biographies

  • Reza Sarwo Widagdo, Universitas 17 Agustus 1945 Surabaya, Indonesia
    Department of Electrical Engineering, Universitas 17 Agustus 1945 Surabaya, Surabaya, Indonesia
  • Puji Slamet, Universitas 17 Agustus 1945 Surabaya, Indonesia
    Department of Electrical Engineering, Universitas 17 Agustus 1945 Surabaya, Surabaya, Indonesia
  • Imam Suri Tauladan, Universitas Riau, Indonesia
    Department of Electrical Engineering, Universitas Riau, Pekanbaru, Indonesia
  • Lutfi Agung Swarga, Universitas 17 Agustus 1945 Surabaya, Indonesia
    Department of Electrical Engineering, Universitas 17 Agustus 1945 Surabaya, Surabaya, Indonesia
  • Bima Gilang Pratama, Universitas 17 Agustus 1945 Surabaya, Indonesia
    Department of Electrical Engineering, Universitas 17 Agustus 1945 Surabaya, Surabaya, Indonesia
  • Izzah Aula Wardah, Universitas 17 Agustus 1945 Surabaya, Indonesia
    Department of Electrical Engineering, Universitas 17 Agustus 1945 Surabaya, Surabaya, Indonesia

Downloads

Published

31-05-2026

How to Cite

Voltage Flicker Analysis due to the Starting of 250 kW Three-Phase Induction Motor at the Karah Pump House, Surabaya . (2026). Jurnal Elektro Dan Mesin Terapan, 12(1), 31-41. https://doi.org/10.35143/elementer.v12i1.7024